Transient Stability Assessment of Multi-Machine Multi-Converter Power Systems

Hugo N. Villegas Pico, Brian Johnson

IEEE Transactions on Power Systems · 2019 · 72 citations · 18 references

DOIFull text

Open access

Concepts

Abstract

Transmission faults caused by recent wildfires in California have induced the disconnection of utility-scale converters in photovoltaic (PV) power plants. Postmortem investigations reported that tripping commands were caused by phase-locked loops (PLLs) and dc-side dynamics, which are typically unmodeled in classical transient stability studies. Since existing simulation packages rely on simplified models that neglect these dynamics, they have a limited capability to predict converter behavior during faults. To address this shortcoming, we set forth a positive-sequence model for PV power plants that is derived from physics and controls first principles. As seen on utility-scale three-phase converters, the model includes PLLs, dc-side dynamics, and closed-loop controllers. Instances of the developed model are integrated into illustrative power systems containing conventional generators. Numerical simulations of the obtained multi-machine multi-converter power systems are assessed via a suitable set of stability and performance metrics.

References

18