MATEC Web of Conferences · 2018 · 22 citations · 0 references
EngineeringElectrical EngineeringCircuit TheoryElectromagnetismPower ElectronicsCurrent-voltage CharacteristicsDistortion AnalysisElectrical MeasurementElectrical TechnologyNonlinear Circuit AnalysisPower QualityCurrent Harmonic DistortionElectric Power Distribution NetworksElectric Power NetworksHarmonic DistortionHarmonic EffectsHarmonicsPower MeasurementVoltage Harmonic Distortion
The results of measurements of the harmonics components of the current, voltage, power of harmonics at the point of connection of electric receivers with a non-linear voltage-current characteristic are considered. It is shown that the amount of electric energy including the non-sinusoidality of the currents and voltages consumed by the non-linear load is less than the amount of the fundamental frequency energy. The difference between them is the harmonic distortion energy that causes extra losses to the electric networks. The voltage harmonic distortions at the measurement point exceed the normative values for 0.4 kV electric networks.