IEEE Transactions on Industrial Informatics · 2018 · 21 citations · 30 references
EngineeringElectrical EngineeringSystems EngineeringEnergy SystemsPower ElectronicsTime Series AnalysisDigital Signal ProcessingFault DetectionFault DiagnosisPower SystemsSmart Grid SystemsSmart GridsCompressive SensingFault IdentificationMedian FilteringPhasor Measurement UnitsSecondary Voltage ControlSecure Control SystemsVoltageVoltage Control
This paper presents an improved secondary voltage control (SVC) methodology incorporating compressive sensing (CS) for a multiarea power system. SVC minimizes the voltage deviation of the load buses while CS deals with the problem of the limited bandwidth capacity of the communication channel by reducing the size of massive data output from the phasor measurement unit (PMU) based monitoring system. The proposed strategy further incorporates the application of a morphological median filter (MMF) to reduce noise from the output of the PMUs. To keep the control area secure and protected locally, mathematical singular entropy (MSE) based fault identification approach is utilized for fast discovery of faults in the control area. Simulation results with 27-bus and 486-bus power systems show that CS can reduce the data size up to 1/10th while the MSE-based fault identification technique can accurately distinguish between fault and steady-state conditions.
30
Image analysis and mathematical morphology
Computer Graphics and Image Processing · 1982 · 8.2K citations