Oil exponent thermal modelling for traction transformer under multiple overloads

Lijun Zhou, Lujia Wang, Haolong Tang, Jian Wang, Lei Guo, Yi Cui

IET Generation Transmission & Distribution · 2018 · 15 citations · 23 references

DOIFull text

Open access

Concepts

Abstract

To quantify the non‐linear variation of top‐oil temperature with load current, and further investigate the key parameters in the thermal model, a model for calculating the oil exponent is proposed in this study. First, a global oil momentum model was established based on the fluid resistance characteristic. Then, based on the heat transfer coupling relationship between the winding, the oil flow, and the radiator (outside air), a set of control equations describing the oil temperature and the oil flow rate was established by using energy conservation. Simultaneously, the top‐oil temperature was recorded from a field traction transformer to verify the physical part of the proposed model. The regression model parameters were identified with the ordinary least‐square estimation so the oil exponent can be calculated naturally. The calculated oil exponent of the traction transformer at a wide range of load was 0.7308, so the accuracy was improved by 9.47% compared with the IEEE/IEC recommended value. Newly updated oil exponent was also verified through a dynamic overload heat run test. It is expected that the proposed oil exponent model can help in estimating top‐oil temperature with more convenience and accuracy, especially in frequent overload conditions.

References