Increased loadability of transformers using natural ester and cellulosic materials as high temperature insulation systems

Vagner Vasconcellos, Alan Sbravati, L.C. Zanetta, Kevin Rapp, Luca Lombini, Stefano Nazzari, Fabio Scatiggio, Andrea Valant

IEEE Electrical Insulation Magazine · 2018 · 23 citations · 5 references

Concepts

Abstract

The use of natural ester–filled transformers started in 1996, with two industrial transformers installed at the Cooper Power System factory to provide power for two core annealing ovens. Investigations conducted according to the IEEE C57.100 accelerated transformer life test method (Lockie Test) [1] and the sealed tube accelerated insulating system material life test method [2]–[4] indicated a possible extension of transformer life, associated with reduction of the paper degradation rate when impregnated with natural ester liquids.