IEEE Transactions on Industrial Electronics · 2018 · 66 citations · 25 references
EngineeringElectrical EngineeringPower ElectronicsRenewable Energy IntegrationRenewable Energy SystemsDistributed Energy ResourcesPower Electronics For Renewable EnergyPower Grid AnalysisPower System StabilityPower SystemsVoltage RegulationAncillary ServicesDistributed GenerationDistributed Generation IntegrationPower RegulationSystem StabilityTest CasesVoltageVoltage Ride-through
Increasing penetration level of distributed generation (DG) units necessitates their participation in supporting power system stability and providing ancillary services. This paper highlights the necessity of supporting the connection voltage by these units under short-term unbalanced voltage sags. To address this, a new regulation scheme, named asymmetrical ride-through (ART), is proposed in this paper. The proposed scheme enforces DG units to properly regulate the voltage within the dynamic limits for three important voltage parameters: positive sequence, negative sequence, and phase voltage magnitude. The main advantages of applying the ART scheme are avoiding unnecessary outages due to temporary unbalanced faults and enhancing the grid stability. As the second contribution, an advanced dynamic voltage support method is also proposed to accurately address the specifications determined in the ART scheme. The successful results of the ART regulation scheme and the proposed dynamic voltage support method are verified using simulation and experimental test cases.
25
Grid Code, high and extra high voltage
E.on Netz · Medical Entomology and Zoology · 2006 · 577 citations