Publication | Closed Access
A Method to Directly Compute Synchronverter Parameters for Desired Dynamic Response
92
Citations
20
References
2017
Year
Parameter IdentificationEngineeringApl ParametersClock SynchronizationPower Electronics ConverterComputer EngineeringSystems EngineeringPower System ControlDesired Dynamic ResponsePower ElectronicsController Parameter ValuesSystem IdentificationApl Dominant ModeFrequency ControlGrid StabilityPower System DynamicPower Systems
This paper proposes a method to directly compute controller parameter values in a synchronverter augmented with a so-called damping correction loop, and in so doing, achieve desired transient and steady-state response. The proposed approach is grounded in a reduced third-order system model that captures pertinent dynamic characteristics of the synchronverter active-power loop (APL), particularly those of the dominant mode. This reduced-order model helps to identify and explain a shortcoming in a previous parameter tuning method. Central to the proposed parameter computation method is to express APL parameters of the original system as closed-form functions of the poles of the reduced-order system. Since the reduced-order model retains dominant-mode dynamic behaviors of the original system, APL parameters can be directly computed according to specified APL dominant mode. Time-domain simulations are provided to validate the accuracy of the reduced-order model and the proposed direct-computation parameter tuning method.