IEEE Transactions on Applied Superconductivity · 2017 · 30 citations · 19 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsElectric CircuitsSuperconducting MaterialsCircuit Breaker ProtectionCommutation TechniquesFault Current LimitingFault Current ProtectionProtection CircuitsRailway Systems EngineeringSuperconducting TapesTraction Systems
The objective of this paper is to propose a dc current interruption technology for railway dc traction systems, consisting of a dc vacuum circuit breaker with a superconducting fault-current limiter (SFCL). To this end, a 1.5-kV dc circuit breaker prototype is designed, involving a dc vacuum circuit breaker and a resistive-type SFCL serially connected. The dc vacuum circuit breaker is developed with a commutation circuit to generate a reverse injection current, and the resistive-type SFCL is composed of yttrium barium copper oxide superconducting tape. An LC current source tested the 1.5-kV prototype, showing that, when the precharged capacitor voltage is 1.5 kV, the prospective current is 47 kA increasing at a rate of 9.4 A/μs. The SFCL limits this current to ~3 kA (peak value), and then, decreases the current to 2 kA after 6 ms, followed by successful clearance via the dc vacuum circuit breaker. The proposed 1.5-kV circuit breaker will successfully clear short-circuit faults up to 47 kA by first limiting the prospective current and then interrupting it.
19
HVDC circuit breakers for HVDC grid applications
K. Tahata, Hiroki Ito, Ryusuke Yamamoto et al. · 2015 · 203 citations