Energies · 2017 · 11 citations · 16 references
EngineeringChemical EngineeringMechanical EngineeringAir ConditioningHeat TransferThermal AnalysisCondensation Heat TransferExtended SurfacesHeat ExchangersHeat Transfer AnalysisHeat Transfer In FluidsThermal DesignAnnular FinsCondensation On Extended SurfacesCondensation RateCondensation TestingFinsFins Heat TransferHeat Transfer RateNatural Convection
This paper presents an experimental investigation on the enhancement of the heat transfer rate of steam condensation on the external surfaces of a vertical tube with annular fins. A cylindrical condenser tube, which is 40 mm in outer diameter and 1000 mm in length, with annular disks of uniform cross-sectional area is fabricated in the manner of ensuring perfect contact between the base surface and fins. A total of 13 annular fins of 80 mm diameter were installed along the tube height in order to increase the effective heat transfer area by 85%. Through a series of condensation tests for the air-steam mixture under natural convection conditions, the heat transfer data was measured in the pressure range of between 2 and 5 bar, and the air mass fraction from 0.3 to 0.7. The rates of heat transfer of the finned tube are compared to those that are measured on a bare tube to demonstrate the enhanced performance by extended surfaces. In addition, based on the experimental results and the characteristics of steam condensation, the applicability of finned tubes to a large condenser system with a bundle layout is evaluated.
16