IEEE Transactions on Power Delivery · 2017 · 37 citations · 10 references
EngineeringElectrical EngineeringCritical Infrastructure ProtectionFault-tolerant SystemsPower ElectronicsEnergy Infrastructure ProtectionPower Grid AnalysisPower QualityProtection SystemsTransmission LinesDistance ProtectionFault ProtectionPhase SelectionProgrammable Relay SystemsProtection RelayingProtective RelayingRelay ProtectionRelays
In this paper, a novel faulted phase selection algorithm is proposed to be used for distance protection applied to half-wavelength power transmission lines. These lines represent an alternating current solution for very-long point-to-point interconnections as an alternative to HVDC. However, no such lines are currently in operation, and if this type of line is to be constructed, it will require its own protection philosophy because of its peculiar characteristics. This paper shows that the fault selection algorithms used in conventional relays do not work properly when applied to half-wavelength lines. The algorithm proposed herein is initially studied in the steady state and ultimately implemented in a programmable protective relay that is tested using a real-time simulator.
10
A Distance Protection Relay for a 1000-kV UHV Transmission Line
Zerui Xu, Shan Huang, Li Ran et al. · IEEE Transactions on Power Delivery · 2008 · 64 citations
David Costello, Karl Zimmerman · 2010 · 47 citations
Engineering, Electrical Engineering, Critical Infrastructure Protection +16