2017 · 12 citations · 12 references
EngineeringElectrical EngineeringElectromagneticsElectromagnetismFinite Element AnalysisFault DetectionGenerator OperationHydropower EngineeringMagnetic Circuit AnalysisMagnetic ComponentsAir Gap AnalysisFinite Element SimulationFlux Distribution AnalysisGeneratorsMagnetic FluxMagnetic Flux DensityMagnetic ModelingPoles
This paper investigates the impact of rotor inter-turn short circuit on the radial magnetic flux density of a large hydro generator. A numerical model based on advanced 2D finite element analysis is used for computing the magnetic flux density with and without inter turn short circuit in rotor winding. At first, the simulated air gap flux density is compared to measurement in order to validate the FEA model. Then two methods based on magnetic flux density in the air gap analysis to detect this fault are presented. Simulation results performed on a 74 MVA industrial hydro generator are presented and discussed. The study showed that the magnetic flux density decreases in the defected pole with the increase of inter turn short circuits. Furthermore, the flux of the defected pole contributes less in the flux of the adjacent poles which facilitate the detection of the defected pole.
12
Liangliang Hao, Junyong Wu, Yanzhen Zhou · IEEE Transactions on Energy Conversion · 2014 · 46 citations