IEEE Transactions on Power Delivery · 2017 · 21 citations · 11 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsFrequency ControlPower Grid AnalysisPower QualityPower System StabilityProtection SystemsVoltage RegulationLow-frequency OscillationsPrimary Voltage ControlTime-domain Disturbance AnalysisTime-domain Response AnalysisTransformer ProtectionTransmission Line TransientsVoltage
A new method to numerically estimate the primary voltage waveform of coupling capacitor voltage transformers is presented. The outcome is a simple digital filter suitable for the frequency range from 10 to 60 Hz, enabling us to recover the transformer primary voltage waveform from its secondary voltage waveform. Unlike the techniques reported in the literature, the method does not depend directly on the transformer topology nor on the operational characteristics of the protected system, once only the coupling capacitor voltage transformer frequency response is required as input. The evaluation of the technique is performed through digital simulations using the Alternative Transients Program and transmission-line data from the Brazilian National Power System Grid. Frequency- and time-domain analysis of two coupling capacitor voltage transformers with different topologies and voltage levels are presented. It is shown that the proposed method is effective for the dynamic correction of low-frequency disturbances that may improve the speed, reliability, and security of the numerical distance relay.
11
Nonlinear Multiobjective Optimization
S. Mardle, K. M. Miettinen · Journal of the Operational Research Society · 2000 · 3.1K citations
Methods for Non-Linear Least Squares Problems
Kaj Madsen, Hans Bruun Nielsen, Ole Tingleff · 1999 · 973 citations
Eran Levy · IRE Transactions on Automatic Control · 1959 · 796 citations
Dynamic compensation of capacitive voltage transformers
Jan Iżykowski, B. Kasztenny, E. Rosołowski et al. · IEEE Transactions on Power Delivery · 1998 · 66 citations