TURKISH JOURNAL OF ELECTRICAL ENGINEERING & COMPUTER SCIENCES · 2017 · 24 citations · 3 references
EngineeringElectrical EngineeringSystems EngineeringCircuit TheoryModel-based Systems EngineeringPower ElectronicsDiagnosisElectric CircuitsElectrical System DiagnosticsFault DetectionFault DiagnosisFault ModelingCircuit Fault AnalysisEarly Fault DetectionElectrical Fault DiagnosisFault AnalysisFault Model AnalysisModel-based Fault DetectionModel-based Fault DiagnosisSystem Fault Diagnosis
In this paper, a dynamic model is developed for high-voltage circuit breakers to extract fault features and causes. Lagrange's method is applied using geometric equations of mechanism components to write the model. Unlike previous approaches, the proposed method reveals and analyzes all types of circuit breaker operating mechanism faults. Early fault detection, which is a vital requirement of the fault diagnosis system, becomes feasible by keeping track of changes in the contact travel curve in the proposed model. Resulting faults in the travel curve are analyzed mathematically in order to find out the exact origin of the fault. Field test results show the accuracy and reliability of the fault detection method.
3
Automated Monitoring and Analysis of Circuit Breaker Operation
Mladen Kezunović, Z. Ren, G. Latisko et al. · IEEE Transactions on Power Delivery · 2005 · 114 citations
A noninvasive diagnostic instrument for power circuit breakers
V. Demjanenko, R.A. Valtin, M. Soumekh et al. · IEEE Transactions on Power Delivery · 1992 · 36 citations