IEEE Transactions on Power Delivery · 2017 · 37 citations · 31 references
EngineeringElectrical EngineeringBuilding DiagnosticsLandscape Change DetectionPower ElectronicsCondition MonitoringDiagnosisDiagnosticsElectrical System DiagnosticsFault DetectionFault DiagnosisFault IdentificationHarmonicsOnline Diagnostics
An online approach based on application of search coil for transformer winding fault detection is presented in this paper. Earlier attempts report use of search coil for the detection of transformer interturn fault. This paper extends application of search coil for detection of winding displacement in addition to interturn fault identification. Experimental results based on specially designed 10-kVA transformer are presented to analyze search coil voltages during healthy and faulty conditions. The algorithm detects phase (U, V , W ), side (LV, HV), and precise location of the fault. Discrimination between interturn fault and winding radial displacement is also achieved by search coil voltage analysis. The results are experimentally verified based on impedance analyzer plots. Experimental analysis indicates that the proposed method is independent of load on the transformer, vector group, nature of winding, balanced or unbalanced source voltage, source voltage harmonics, inrush, and overexcitation conditions.
31