Electrical EngineeringEngineeringPower Grid OperationSmart GridGrounding ConductorElectrical TransmissionSubstation WorkGrounding GridSystems EngineeringElectric Power TransmissionComputational ElectromagneticsGrid ConfigurationElectric Power DistributionConfiguration DetectionElectromagnetic Compatibility
Optimizing the grounding grid configuration is an effective approach to improve the performance of grounding grid. On the other hand, configuration of grounding grid is necessary for some defect diagnosis method to detect the faults existing in grounding conductors. This paper employs the transient electromagnetic (TEM) method to draw the configuration of a substation grounding grid. The surface magnetic field is recorded by receiver coils above the grounding grid. Based on the regular distribution characteristics of a recorded magnetic field, the grounding conductor is accurately located from the curve of magnetic intensity. The complete process of configuration detection of the grounding grid is described in detail. After fast inversion calculation of the recorded magnetic field, the equivalent resistivity is obtained. The configuration of the grounding grid will be clearly and accurately shown in the contour map and three-dimensional (3-D) surface map of equivalent resistivity. Model study is performed, and a field test is also conducted. The results are in good agreement to demonstrate the effectiveness of TEM method for configuration detection of the substation grounding grid.