Room Air Disinfection by Ultraviolet Irradiation of Upper Air

Richard L. Riley, Solbert Permutt, James E. Kaufman

Archives of Environmental Health An International Journal · 1971 · 36 citations · 2 references

Concepts

Abstract

Room air disinfection by upper air UV was studied in relation to temperature gradients. When upper air temperature minus lower air temperature ranged between +7 and -2 F, the rate of disappearance of test organisms from the lower air, with two UV fixtures operating, averaged 33 equivalent air changes per hour (AC/hr), and when the temperature difference ranged between -3 and -5 F, the rate of disappearance averaged 83 AC/hr. Estimates indicated that the rate of air exchange between the upper and lower parts of the room averaged about 25 AC/hr when air entering at the ceiling was warmer than lower room air and exceeded 125 AO/hr when air entering at the ceiling was 3 F or more cooler than the air in the lower part of the room.

References

2