Comparative study between PI and fuzzy-logic controllers for three-phase grid-connected photovoltaic systems

M.S. Omar, Amgad A. El‐Deib, A. L. El Shafei, M. A. El.rhman, Mohamed E. Abdallah

2016 · 17 citations · 16 references

Concepts

Abstract

This paper presents a Matlab/Simulink model of a 300 KW grid connected photovoltaic (PV) system. The system includes a 300 KW PV array, a maximum power point tracking boost converter using perturbation and observation (P&O) method and a grid connected inverter with its control system. An L-filter is designed to smoothly connect the inverter to the utility grid. The boost converter controlled by a P&O algorithm is responsible for extracting the maximum power available to the PV array at any atmospheric conditions. The grid connected inverter is responsible for maintaining the DC link voltage constant. To accomplish the grid connected inverter task, a cascaded control structure is used; the outer control loop is the DC link voltage loop while the inner control loop is the direct axis inverter current component. A reactive power controller is used also to support the grid with a reactive power from the reserve inverter capacity. To control the reactive power transferred to the grid the quadrature axis inverter current component is controlled. A classical proportional-integral (PI) and fuzzy logic controller are used to control the DC link voltage, direct axis current and quadrature axis current component. This paper also analyzes the characteristic of the power converter performance under PI control and fuzzy logic control connected to a very weak grid with minimum short circuit ratio (SCR).

References

16