IEEE Transactions on Power Electronics · 2016 · 121 citations · 40 references
EngineeringElectrical EngineeringEnergy EconomicsEnergy SystemsPower ElectronicsBattery SystemsConverter TopologiesEnergy StorageEnergy Storage IntegrationPower System ReliabilityPower SystemsBattery Energy StorageBattery Pack IntegrationCascaded H-bridge ConvertersEnergy Storage Reliability AnalysisEnergy Storage System ModelingEnergy Storage SystemsEnergy Storage TechnologiesPerformance Degradation
This paper presents a method for evaluating grid-connected battery energy storage system (BESS) designs. The steady-state power losses of the grid interface converter, the battery pack, and the balancing circuit are calculated. The reliability of each complete system is calculated using a Markov-based modeling approach that takes into account the built-in redundancy of the system as well as performance degradation caused by faults. Finally, a simple economic analysis based on capital cost and efficiency is used to provide a basis for direct comparison between competing system designs. Three design options for a 1-MW 1-MWh BESS connected at 11 kV are compared: a conventional BESS using parallel low voltage power blocks, a BESS using a high-voltage intelligent battery pack, and a BESS using a cascaded H-bridge converter. The results of the analysis indicate that additional power electronics included in the battery pack as part of the intelligent battery pack and H-bridge designs can enhance the reliability of the BESS by an order of magnitude under typical conditions, without increasing the overall cost of the system.
40
Passive and active battery balancing comparison based on MATLAB simulation
Mohamed Daowd, Noshin Omar, Peter Van den Bossche et al. · 2011 · 446 citations