Gao dianya jishu · 2013 · 18 citations · 0 references
EngineeringElectrical EngineeringPhysicsAcoustic DesignAcousticsAir ConditioningNoiseNoise MeasurementNoise TestingA-weighted Sound MeasurementCommissioningNoise Emission MeasurementNoise Source CharacterizationOctave Band AnalysisOctave-band AttenuationSound Power MeasurementSpectral Characteristics
In order to obtain the boundary noise level in ultra-high voltage(UHV) AC substation,we measured the noise levels of transformer and reactor in station,as well as their spectral characteristics,attenuation characteristics and relationship to the power load.The measurement was mainly performed in a substation of UHV Test Demonstration Project in China,in its normal operation and load commissioning period,respectively.The measurement results were further analyzed.It is concluded that the noise of transformer is mainly at low and medium frequencies,it is more influenced by cooling fan,and it has an approximate positive correlation with the power load.The energy of reactor noise concentrates on the 1/3 octave band centered at 100 Hz,while has little correlation with the power load.The noise of transformer and reactor slowly decreases with increasing the distance from equipment,so the transformer and reactor should not be placed close to environmentally-sensitive sound areas.In addition,we verified the A-weighted sound power levels of UHV transformers and reactors under normal load to be approximately 103 dB and 97 dB,respectively;we also obtained the parameters of sound power level in 1/3 octave band of the sound source,providing basic data for predictions and evaluations of substation noise.