FREQUENCY DOMAIN METHOD OF FAULT LOCATION BASED ON PARAMETER IDENTIFICATION--USING ONE TERMINAL DATA

Suonan Jiale

Proceedings of the Csee · 2005 · 12 citations · 0 references

Concepts

Abstract

This paper proposes the spectral equation of fault network with the fault distance, fault resistance, the opposite terminal system resistance and inductance as unknown parameters. The fault can be located accurately based on the local voltage and current measurements by identifying the above parameters and solving the network equations for different frequencies. By identifying the actual opposite impedance, this algorithm eliminates its influence on the fault location accuracy, which is the main source of error for conventional fault location methods using one terminal data. The method for calculating spectrum from sampled data is devised. EMTP simulations show the validity of this fault location method, and its accuracy higher than the existing algorithms based on one terminal data. This fault location method can be applied in R-L model or distribution model transmission lines. With the development and application of optical transform, it is hopeful to put this method into practice.