Effects of temperature and velocity on fouling by municipal secondary effluent in plate heat exchangers

Ou Hongfei

Journal of Tsinghua University(Science and Technology) · 2009 · 10 citations · 0 references

Concepts

Abstract

The fouling characteristics of municipal secondary effluent in plate heat exchangers were investigated in the field. The fouling resistance and flow pressure drop were monitored for various heat pump working conditions. The tests focused on the effects of temperature and velocity on the initial stage of fouling formation. The experiments show that the fouling formation in the plate heat exchanger consists of an initial period, a growth period, and an asymptotic layer thickness period. The initial period lasts 3.5~8 days, with temperature increase, increasing the fouling formation rate, so the fouling grows faster in the spring and summer. The competition between growing and spalling is related to the velocity during fouling.