Gao dianya jishu · 2013 · 13 citations · 0 references
EngineeringMechanical EngineeringHeat TransferPower ElectronicsThermal AnalysisHeat Transfer ModelingTemperature MeasurementThermal ManagementThermal SimulationHeat Conduction In WindingsTemperature Distribution AnalysisTemperature Distribution ModelingTemperature Field AnalysisTemperature Field EstimationTemperature MonitoringTemperature Rise AnalysisWinding Thermal Analysis
In order to reflect the temperature inside cast resin dry-type transformers more accurately,temperature rising of a dry-type transformer was mathematically calculated according to power losses of the transformer.Meanwhile,by using the software ANSYS,a temperature field of the dry-type transformers was also simulated.Consequently,the temperature distribution of iron core and windings of the transformer were analyzed.A temperature monitoring system was established in a dry-type transformer in sub-section post,and the temperatures of three phases of the transformer were obtained,which were 62.19,63.92 and 62.57°C.According to the comparison among the theoretical calculation,the simulation results,and the actual measurement,it is concluded that the hottest spot in an operating dry-type transformer is in the low-voltage winding at 70% height from the bottom.The hottest spot is normally considered the weak link of an operating dry-type transformer,and this is a practical reference for establishing effective monitoring on dry-type transformers.