Temperature Rise Analysis and Calculation of Cast Resin Dry-type Transformers

He Wei

Gao dianya jishu · 2013 · 13 citations · 0 references

Concepts

Abstract

In order to reflect the temperature inside cast resin dry-type transformers more accurately,temperature rising of a dry-type transformer was mathematically calculated according to power losses of the transformer.Meanwhile,by using the software ANSYS,a temperature field of the dry-type transformers was also simulated.Consequently,the temperature distribution of iron core and windings of the transformer were analyzed.A temperature monitoring system was established in a dry-type transformer in sub-section post,and the temperatures of three phases of the transformer were obtained,which were 62.19,63.92 and 62.57°C.According to the comparison among the theoretical calculation,the simulation results,and the actual measurement,it is concluded that the hottest spot in an operating dry-type transformer is in the low-voltage winding at 70% height from the bottom.The hottest spot is normally considered the weak link of an operating dry-type transformer,and this is a practical reference for establishing effective monitoring on dry-type transformers.