Power System Technology · 2008 · 18 citations · 0 references
EngineeringElectrical EngineeringPower ElectronicsRenewable Energy SystemsWind EngineeringDistributed Energy ResourcesPower Grid AnalysisPower System StabilityRenewable Energy Power ConversionVoltage RegulationWind Energy SystemsConvertersGeneratorsGrid Stability AnalysisPower Grid RegulationVoltage StabilityVoltage Stability ControlWind Power SystemsWind Turbine Power Converters
Large-scale wind farms located at the end of power grid will probably greatly impact the voltage stability of power grid. To ensure the secure operation of wind farms, according to the conversion character of wind power and operation performance of asynchronous generators a mathematical model for wind farm and related power gird under large disturbance is built, and the voltage stability of wind farm and related power grid is calculated while short-circuit fault occurs. By means of numerical simulation, the mechanism of power grid stability failure due to connecting wind farm with it is revealed. It is pointed out that the revolution speed of wind turbine generation unit is the principal parameter to impact the operating characteristics of the two energy converters, i.e., wind turbine and asynchronous generator, so the control of revolution speed increment of wind turbine is the key problem in order to maintain power grid voltage stability after large-scale wind farm is connected with power grid. The capacity of wind turbine generation unit near the faulty location, the position of faulty point and the duration of the fault are the main factors impacting voltage stability after the short-circuit fault occurs. The strategy and measures to ensure the voltage stability of power with wind farm connected are proposed.