Synchronous Instability Mechanism of P-f Droop-Controlled Voltage Source Converter Caused by Current Saturation
276
Citations
4
References
2016
Year
Electrical EngineeringEngineeringInfinite BusLarge DisturbancesPower Electronics ConverterCurrent SaturationPower System ControlVirtual PowerPower ElectronicsSynchronous Instability MechanismGrid StabilityPower System TransientPower SystemsStability
Under large disturbances, P-f droop-controlled voltage source converters may lose synchronous stability, just like synchronous generator. Moreover, the current limitation leads to a more complicated instability mechanism and decreases stability margin greatly. This letter describes a virtual power angle instability problem and analyzes its mechanism from the virtual power angle characteristic curves of a converter with respect to an infinite bus. Simulation verifies the rationality of the analysis.