2011 · 23 citations · 2 references
ArchitectureArchitectural EngineeringBuilding ScienceBuilt EnvironmentEnergy ManagementThermal ComfortBuilding Energy PerformanceBuilding Energy SystemsBuilding Life-cycle AssessmentBuilding PerformanceBuilding Thermal PerformanceEnergy UseBuilding Energy Consumption AnalysisBuilding Energy Performance IndicatorsEnergy ConsumptionEnergy PerformanceEnergy Performance EvaluationEnergy Performance IndexEnergy Use AnalysisTropical Climate Change
The study conducted is to identify building energy index (BEI) in a large scale educational hospital in tropical climate in Malaysia. The built up area of 247000 m.sq. In order to calculate BEI, the total energy consumption for different source of energy was calculated. The calculated BEI for HUKM is 245 kwh/m2. Electricity is the main source energy that is around 75% of total energy consumption. Electricity usage for each zone was assessed also it is found that electricity using for chillers is more than 40 % of total electricity consumption.
2
An end-use energy analysis in a Malaysian public hospital
R. Saidur, M. Hasanuzzaman, S. Yogeswaran et al. · Energy · 2010 · 119 citations
Architecture, Health Services Administration, Energy Management +13