IEEE Power and Energy Technology Systems Journal · 2016 · 45 citations · 15 references
EngineeringElectrical EngineeringEnergy SystemsRenewable Energy IntegrationRenewable Energy SystemsDistributed Energy ResourcesPower Grid AnalysisPower SystemsRenewable EnergySolar Energy SystemsSolar Photovoltaic SystemsDistribution Network ModelingHarmonic Loading EffectsImpact AnalysisLoad Flow AnalysisPhotovoltaic System SimulationPhotovoltaic SystemsResonanceVoltage Harmonic Distortion
This paper presents one of the first studies of the harmonic impact of a significantly large photovoltaic (PV) solar farm of 20 MW in a utility distribution system. This solar farm is a constituent of the 80-MW PV solar farm in Sarnia, Ontario, which is so far the largest solar farm in Canada. The utility network is modeled in detail using the commercial grade PSCAD/EMTDC software, which is validated through load flow studies conducted by CYME software and correlated with SCADA measurements. The validated network model is used for network resonance study and harmonics impact analysis of the solar farms under different network conditions. The harmonics data instrumented for several months were provided by the transmission utility at the two solar farm units and at the main feeder substation. These data were utilized for extensive harmonic impact studies with widely different short-circuit levels and network resonance conditions. This paper presents the detailed procedure adopted for performing such harmonic impact studies. It is concluded that this large solar farm may not cause any substantial voltage distortion on the distribution network during steady-state operating conditions. However, recommendations are made for utilities to perform such studies to ensure the safe operation of critical loads.
15