Numerical Analysis and Optimization of Lobe-Type Magnetic Shielding in a 334 MVA Single-Phase Auto-Transformer

Longnv Li, W. N. Fu, S. L. Ho, Shuangxia Niu, Yan Li

IEEE Transactions on Magnetics · 2014 · 22 citations · 9 references

Concepts

Abstract

In this paper, the influences of the lobe-type magnetic shielding in a transformer in terms of its leakage fields, stray losses in structural parts, shielding losses, and short-circuit impedance are examined using 3-D non-linear frequency-domain finite element method. An ODFS-334 MVA/500 kV single-phase auto-transformer is used as the prototype model under study. The magnetic shielding geometry of the transformer is optimized with its stray losses minimized based on 3-D non-linear finite element analysis. To validate the feasibility of the proposed model and method, experimental data and simulation results are compared and reported.

References

9