Comparison of Partial Discharge Characteristics in SF<sub>6</sub>Gas Under AC and DC

Hyang-Eun Jo, Guo‐Ming Wang, Sun-Jae Kim, Gyung-Suk Kil

Transactions on Electrical and Electronic Materials · 2015 · 13 citations · 6 references

DOIFull text

Open access

Concepts

Abstract

In this paper, parameters related with partial discharge (PD) were analyzed in SF<sub>6</sub> gas under AC and DC voltages. Three electrode systems (protrusion on conductor, protrusion on enclosure, and free particle) were fabricated to simulate PD defects in a gas-insulated switchgear (GIS). All electrode systems were filled with SF<sub>6</sub> gas at 0.5 MPa. PD pulses were detected using an oscilloscope and a data acquisition (DAQ) based on IEC 60270. To analyze the PD characteristics under AC and DC voltages, parameters such as discharge inception voltage (DIV), discharge extinction voltage (DEV), pulse magnitude, repetition rate, and T-F map were compared. From the experimental results, PD was revealed to have different characteristics under AC and DC, and these results may be useful for diagnosis of power facilities operated under HVDC.

References

6