Jurnal Teknologi · 2015 · 10 citations · 13 references
Public HealthInfectious DiseasesAir PollutionAir Pollution ControlAir Quality ManagementAir FiltrationAir PollutantsAir Pollution MeasurementAir QualityAir SamplingParticulate MatterAirborne Particle MonitoringAirborne Particulate MeasurementField Measurement ProceduresField Measurement ProtocolsHigh-efficiency Particulate Air (Hepa) FiltersParticulate Contamination AssessmentParticulate Matter MeasurementParticulate Matter Monitoring
In a hospital operating room, adequate air flow and cleanliness are crucial to protect the patient from surgical site infection (SSI) during a procedure. The probability of the patient to get the infection is related to the concentration of bacteria carrying particles inside the room. This paper presents a field measurement study to quantify the concentration of particulate matters (PM) in a hospital operating room which complies with the ISO Class 7 requirements. The operating room was equipped with High Efficiency Particulate Air (HEPA) filters and a vertical laminar air flow (LAF) system. The measurements were conducted at three height levels from the floor namely 1.2 m, 1.8 m and 2.4 m. The data was logged at a rest condition, in accordance to the ISO 14644-1 requirements. A HPC300 particle counter was used to measure the concentrations of particulate matters namely PM0.5, PM1 and PM5. The results show that the concentrations of all particulate matters were higher at the height level of 1.2 m compared to other height levels. The concentration of PM0.5 was relatively higher than PM1 and PM5 in the vicinity of operating table.
13
Magda Diab‐Elschahawi, Jutta Berger, Alexander Blacky et al. · American Journal of Infection Control · 2011 · 95 citations