OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1996 · 33 citations · 0 references
ArchitectureArchitectural EngineeringBuilding ScienceHeat TransferHeatingThermal ComfortBuilding Thermal PerformanceEnergy UseHeat Transfer In BuildingsLoad CalculationResidential Water UseThermal Performance AssessmentBuilding Thermal Load AnalysisCommercial Building Water ConsumptionHeating FacilitiesHot Water ConsumptionHot Water HeatingHot Water Load ProfilingResidential Heating LoadResidential Water Consumption
This paper presents long-term test data obtained in 20 commercial buildings and 16 residential sites. The information illustrates the effects of variations in hot water load determinants and the effect on energy use. It also is useful as a supplement to the load profiles presented in the ASHRAE Handbooks and other design references. The commercial facilities include supermarkets, fast-food restaurants, full-service restaurants, commercial kitchens, a motel, a nursing home, a hospital, a bakery, and laundry facilities. The residential sites ere selected to provide test sites with higher-than-average hot water use. They include 13 single-family detached residences, one 14-unit apartment building, and two apartment laundries. Test data are available at measurement intervals of 1 minute for the residential sites and 15 minutes for the commercial sites. Summary data in tabular and graphical form are presented for average daily volumetric hot water use and cold inlet water temperature. Measured cold inlet water temperature and volumetric hot water use figures are compared to values typically used for design and analysis. Conclusions are offered regarding the effect of cold water inlet temperature and variations in hot water use on water-heating load and energy use. Recommendations for the use of the information presented in water-heatingmore » system design, performance optimization, and performance analysis conclude the paper.« less