2015 · 13 citations · 5 references
Electrical EngineeringEngineeringElectrical TransmissionTransmission LineElectrophysiologyTriple CircuitInduced Sheath VoltageCircuit AnalysisMetallic Cable ShieldElectrical Insulation
Flow of current in a cable conductor generates a magnetic field which could induce current flow in the metallic cable shield or sheath. This paper examines induced voltage calculation in multi-circuit of the cables with the hope of proposing new methodology for induced sheath voltage computation in metallic shield of a single-core power cable operating in a triple circuit. This study considers a few examples to demonstrate the method of examining the induced voltage in single, double and triple-circuits. The calculated values for induced voltages were 0.079 V/m, 0.074 V/m and 0.068 V/m for triple, double and single circuit. It is found that induced sheath voltage increased with the increase in number of the cables.
5
Calculation of sheath voltage of underground cables using various configurations
Muhammad Shaban, Swee Peng Ang, William Voon et al. · 2014 · 10 citations