1986 · 15 citations · 1 references
EngineeringElectrical EngineeringCircuit TheoryEnergy SystemsPower ElectronicsConverter TopologiesDc-ac InvertersPower QualityPower System StabilityPower SystemsUninterruptible Power Supply SystemsDynamic Performance AnalysisHigh-frequency InvertersInverter DesignLoad DistributionParallel Ups OperationPower Electronics DevicesSingle-phase InvertersUps Topologies
The active and reactive load distribution between n paralleled single-phase UPS inverters is equalized by virtue of n − 1 load sharing control loops. The approach permits the construction of UPS systems of any desired power rating at maximum utilization of the power components. The method of harmonic cancellation decreases the switching frequency of the power devices while maintaining good dynamic performance. The design details of a 45 kVA UPS inverter system with 150 % steady-state overload capability are presented. The performance at various operating conditions is illustrated by oscillograms.
1
Large Parallel UPS Systems Utilizing PWM Technology
John J. Reed, Naresh Sharma · 1984 · 15 citations