2015 · 15 citations · 9 references
Natural SciencesElectrical EngineeringPhysicsComputational ElectromagneticsElectromagneticsElectromagnetismLightning CurrentLightning PhysicsMethod Of MomentsPower Grid AnalysisThunderstorm ElectricityThunderstorm ElectrificationElectric Power System ModelingElectromagnetic Transient SimulationGrid-connected Photovoltaic SystemsGroundingGrounding SystemsImpedance MatrixPower System ModellingRational Function Approximation
The paper adopts a comprehensive modeling technique to investigate the effect of frequency-dependent characteristics of grounding system in a grid-connected photovoltaic (PV) system on the overvoltages caused by lightning strikes on the nearby overhead line. In this technique, the frequency response of grounding system is determined using an electromagnetic approach based on the method-of-moments (MoM) solutions of the governing Maxwell's equations. To evaluate the resultant overvolatges on the key components of PV systems, the electromagnetic transients program (EMTP) is used where the grounding system is represented by an appropriate state-space model. The model is derived by approximating the frequency response of the MoM impedance matrix by a rational function based on the vector fitting method. Simulated results obtained for a typical grid-connected PV system show that when a lightning surge hits the grid, the values of overvoltages produced in the PV system can exceed those predicted by the conventional resistive model of grounding system.
9
Kazuo Yamamoto, Shunichi Yanagawa, Koichi Yamabuki et al. · IEEE Transactions on Power Delivery · 2010 · 107 citations