OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1996 · 16 citations · 0 references
EngineeringChemical EngineeringEnvironmental EngineeringAir ConditioningHeat TransferThermodynamicsAdsorption ProcessesAir Conditioning SystemsCooling SystemsHeat Transfer FundamentalsHeat Transfer ModelingRefrigeration SystemsCooling System ThermodynamicsCycle TimeGas AdsorptionHeat Transfer Coefficient EstimationHeat Transfer MechanismsThermal Boundary ConditionsZeolite AdsorbentsZeolite Sorbents
Adsorptive air conditioning represents a potential alternative to chlorofluorocarbon (CFC) systems. But to compete with other systems, adsorption systems must exhibit sufficient figures of merit and energetic densities. An analytical study to predict the overall heat transfer coefficient in an adsorber has been conducted and is presented here. This study, based on a method-of-moment analysis, shows the influence of three parameters limiting the heat transfer in adsorbent beds. Heat transfer in adsorbent beds has been intensified. Using new consolidated materials, the machine utilizes two uniform temperature adsorbent beds in a cycle that incorporates both heat and mass recovery. It uses a zeolite-water pair. It is designed to produce 3 kW of cooling. Expected cooling performances are 300 W/kg of adsorbent with a coefficient of performance (COP) close to 0.8 and a cycle time of 20 minutes. The thermal conditions used to test the cycle are: the heater, 220 C; the cooler, 40 C; and the evaporation temperature, 3 C.