Geotherm. Energy Mag.; (United States) · 1984 · 15 citations · 0 references
EngineeringMechanical EngineeringGeotechnical EngineeringHeat TransferHeatingGeothermal Energy SystemsHeat ExchangersHeat PumpsGeothermal CorrosionGeothermal HeatingHeat PipesPlate Heat ExchangersSpace HeatingSpace Heating DesignSubmersible Pumps
Geothermal well pumps are normally either the submersible type or the turbine type. Submersibles are necessary if the lift is high, say 240 m (300 ft) or more. If a turbine pump can be used, a variable speed driver should be considered. These drivers permit no load starting, reduce shock and vibration, and minimize horsepower requirements. In the range of flow between 20 % and 60% of design, the power savings is about 40% when compared to regulating flow by throtting. Plate heat exchangers are less expensive and more effective than tube heat exchangers in the usual geothermal applications. They can be used as the key component in a two loop system to minimize the effect of corrosion and deposits. Many types of nonmetallic pipes are available that are suitable for geothermal service. Limiting consideration for each type is the geothermal water temperature. Burying a pipeline achieves an insulating effect. This can be improved by selective backfilling, and of course, use of insulated pipe. In addition to economic considerations, the minimum acceptable delivered water temperature must be considered. Delivered water temperatures drop drastically at low flows. Space heating can be accomplished using geothermal water as low as 29.4/sup 0/C (85/supmore » 0/F). Methods used are dependent on the temperature of the water available. Finned tubes in forced air ducting are a very effective method of heating, using water as low as 40.6/sup 0/C (105/sup 0/F), achieving approach to room temperature of 5.6/sup 0/C (10/sup 0/ F) with the discharge water.« less