Evaporation Heat Transfer and Pressure Drop in Ozone-Safe Refrigerants and Refrigerant-Oil Mixtures

John Panek

Illinois Digital Environment for Access to Learning and Scholarship (University of Illinois at Urbana-Champaign) · 1992 · 26 citations · 7 references

Full text

Open access

Concepts

Abstract

The ozone-depleting effect of chlorofluorocarbons (CFC's) has caused an intensive search for alternative
\nfluids to be used in vapor-compression refrigeration and air-conditioning machinery. A promising replacement for
\nCFC-12 has been identified, hydro-fluorocarbon (HFC) 134a. This new refrigerant is expected to have different heat
\ntransfer and pressure drop characteristics than CFC-12 when changing phase in the evaporator component. The
\npresence of oil for lubrication purposes may also have an effect. Heat transfer coefficients and pressure drops of
\nHFC-134a and CFC-12 boiling in horizontal tubes were measured. Polyalkylene Glycol (PAG) and Ester oils were
\nmixed with HFC-134a to determine effects of various concentrations of oil. Tests were run in the mobile airconditioning
\nrange of temperature (5??C), mass fluxes (100 to 500 kg/m2s), and heat fluxes (5 to 30 kW/m2). Various
\ninlet qualities to the test section were studied, from 20 to 60 percent. Comparison of data with previous correlations
\nfrom the literature is made, and a new correlation for pure refrigerant heat transfer is proposed.

References

7