Publication | Closed Access
Modelling and experimental performance analysis of solar-assisted ground source heat pump system
425
Citations
37
References
2015
Year
EngineeringEnergy EfficiencyEnergy ConversionHeat PipePhotovoltaic Power StationPhotovoltaicsExperimental Performance AnalysisSystems EngineeringHeat PumpRenewable Energy SystemsSolar Energy UtilisationSolar PowerHeat TransferSolar CoolingSpiral LoopCoiled LoopEnergy ManagementCivil EngineeringThermal EngineeringArtificial Neural Network
In this study, slinky (the slinky-loop configuration is also known as the coiled loop or spiral loop of flexible plastic pipe)type ground heat exchanger (GHE) was established for a solar-assisted ground source heat pump system. System modelling is performed with the data obtained from the experiment. Artificial neural network (ANN) and adaptive neuro-fuzzy inference system (ANFIS) are used in modelling. The slinky pipes have been laid horizontally and vertically in a ditch. The system coefficient of performance (COPsys) and the heat pump coefficient of performance (COPhp) have been calculated as 2.88 and 3.55, respectively, at horizontal slinky-type GHE, while COPsys and COPhp were calculated as 2.34 and 2.91, respectively, at vertical slinky-type GHE. The obtained results showed that the ANFIS is more successful than that of ANN for forecasting performance of a solar ground source heat pump system.