Lightning effects on distribution transformers and reliability of power distribution systems in Colombia

Harby Daniel Aranguren, Claudia Tovar, Juan Inampues, Jesús A. López, Edison Soto, Horacio Torres

Ingeniería e Investigación · 2015 · 10 citations · 3 references

DOIFull text

Open access

Concepts

Abstract

<span>Failure rates of rural power systems are statistically studied based on lightning parameters and a two-state weather model (normal and <span>adverse). Lightning information is matched with geographical coordinates of 251,024 power transformers in a vast area in central <span>Colombia. An important portion of transformers present failure rates 45 times higher than normal, and very large overhead lines, <span>representing a high portion of the total system, present very high failure rates over 75 times higher than in normal weather conditions.</span></span></span><br /><br class="Apple-interchange-newline" /></span>

References

3