Heat Transfer and Flow Characteristics of R-22, R-321R-125 and R-134a in Smooth and Micro-Fin Tubes

B.R. Christoffersen

Illinois Digital Environment for Access to Learning and Scholarship (University of Illinois at Urbana-Champaign) · 1993 · 12 citations · 18 references

Full text

Open access

Concepts

Abstract

Local in-tube heat transfer coefficient and pressure drop data have been collected for
\nR-22 and two potential replacements, R-134a and R-32/R-125, in both smooth and micro-fin
\ntubes. The smooth tube data indicates that the heat transfer coefficient of R-32/R-125 is as
\nmuch as 50% higher than that of R-22 for similar conditions, while the pressure drop is 30%
\nless. R-134a generally shows a weaker performance than R-22 in terms of higher pressure
\ndrop while exhibiting similar heat transfer performance. The micro-fin tube data indicates
\nthat the most significant gains in heat transfer are realized at low mass fluxes were the microfin
\ntube seems to promote tube wall wetting. The study of return bend pressure drop
\nindicates that the pressure drop due to return bends may be as much as 30% of the total
\npressure drop in a typical serpentine evaporator. A computer model has been developed and
\nused to simulate the evaporator component in order to compare the three refrigerants. R-
\n32/R-125 outperforms R-22 in the simulation while R-134a shows the weakest performance.
\nThe computer model is also used to perform an optimization of evaporator tube length and
\ndiameter. A clear optimum is difficult to ascertain from the model, but the optimum tube
\nlength is clearly a strong function of pressure drop which increases very rapidly as the tube
\ndiameter is decreased. Therefore, a slight undersizing of the tube diameter requires a much
\nlonger tube, so a conservative design of oversizing the tube diameter is preferable.