OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1997 · 28 citations · 1 references
ArchitectureBuilding ScienceSystems EngineeringAir ConditioningEnergy SystemsHvac SystemsAir Conditioning SystemsBuilding Energy PerformanceBuilding Energy SystemsBuilding Thermal PerformanceEnergy UseLoad CalculationAir Conditioning PerformanceBuilding Energy DemandCoolingEnergy Efficiency In HomesEnergy Use AnalysisHvac Energy UseHvac System SizingResidential Energy Efficiency
Installed central air conditioning system capacities in 368 recently-built Florida homes were compared with Manual J load values calculated from house audit data. Over 50% of the homes had installed systems with a cooling capacity greater than 120% of the calculated Manual J value. Thirty-one percent of the 78 heat pump homes in this study had installed heating capacity greater than 120% of the calculated Manual J value. Using submetered data from the air conditioning system, a definite increase in peak energy use was observed for systems sized over 120% of Manual J calculations. The effect of system sizing on the system run-time fractions of units is shown. The homes that had units sized smaller than the calculated Manual J value tended to have higher percentages of maximum hourly run-time fractions. There was little difference in binned percentages of large runtime fractions between homes with installed-to-calculated ratios of 1.0 to 1.2 and those with installed-to-calculated ratios greater than 1.2.