2008 · 40 citations · 1 references
Natural SciencesChemistryMaterials ScienceCorrosion ScienceElectrochemistryMetallurgyCorrosion ControlCorrosion EngineeringCorrosion ProtectionCorrosion-resistant MaterialsMetal SulfidesSulfur ChemistryCopper CorrosionDisulfide ChemistrySulfur-bearing Species
Dibenzyl Disulfide (DBDS) is one of several sulfur compounds known to cause copper corrosion in transformers under certain circumstances. Remedial processes such as adsorbents, absorbents, and oil change-out have been known to reduce the concentration of DBDS in the oil. However, if not destroyed or removed below several mg/kg (ppm), breakdown of the DBDS to benzyl mercaptan or a DBDSCopper complex can still cause corrosion of copper and the formation of copper sulfide. Passivators are also being used to protect the copper against corrosive sulfur attack but does not remove or destroy any corrosive sulfur species or those sulfur compounds that can become corrosive. This paper discusses a process in which the destruction of DBDS is complete to below 1 mg/kg, can be performed at the transformer, and the oil reused in the same unit.
1