IEEE Power Engineering Review · 2002 · 34 citations · 1 references
EngineeringElectrical EngineeringHeat TransferPower ElectronicsThermal AnalysisHigh-frequency Power ConversionInsulation SystemsPower System ReliabilityThermal InsulationThermal ManagementThree-phase CircuitsFull Load ConditionHot Spot Temperature PredictionLeakage FluxLimiting Factor AnalysisThree-phase TransformersTransformer Insulation
Harmonic frequency leakage flux can be a limiting factor in three-phase, 3-winding HVDC converter transformers. Investigation of a three-phase, three-winding, 240 MVA converter transformer failure indicated the failure was caused by harmonic fluxes. Calculations indicated that the magnitudes of these harmonic fluxes to be approximately 45% of the power frequency leakage flux for the transformer, and are little affected by the transformer impedance or the converter firing angle. A study of the failed transformer loading during its life was made and a calculation made of the hot-spot temperature considering various insulation half-life factors. Based on published information on insulation half life factors it was estimated that at full load the hot spot temperature of the transformer was about 159°C. From examination of the insulation in the hot spot area, this estimate of hot spot temperature was considered reasonable.
1