Time Delay SystemReal-time ControlEngineeringSmart GridDelay-dependent Robust MethodComputer EngineeringSystems EngineeringClosed-loop Lfc SchemePid ControlPower System ControlLoad ControlPower System DynamicTime DelaysController TuningFrequency ControlPower SystemsStability
The usage of communication channels introduces time delays into load frequency control (LFC) schemes. Those delays may degrade dynamic performance, and even cause instability, of a closed-loop LFC scheme. In this paper, a delay-dependent robust method is proposed for analysis/synthesis of a PID-type LFC scheme considering time delays. The effect of the disturbance on the controlled output is defined as a robust performance index (RPI) of the closed-loop system. At first, for a preset delay upper bound, controller gains are determined by minimizing the RPI. Secondly, calculation of the RPIs of the closed-loop system under different delays provides a new way to assess robustness against delays and estimate delay margins. Case studies are based on three-area LFC schemes under traditional and deregulated environments, respectively. The results show that the PID-type controller obtained can guarantee the tolerance for delays less than the preset upper bound and provide a bigger delay margin than the existing controllers do. Moreover, its robustness against load variations and parameter uncertainties is verified via simulation studies.