IEEE Transactions on Industry Applications · 2007 · 26 citations · 9 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsElectrical System DiagnosticsPower QualityCurrent Measurement AccuracyRelay ProtectionSaturation
Previously, ANSI/IEEE relay current transformer (CT) sizing criteria were based on traditional symmetrical calculations that are usually discussed by technical articles and manufacturers' guidelines. In 1996, IEEE Standard C37.110-1996 introduced (1+X/R) offset multiplying, current asymmetry, and current distortion factors, officially changing the CT sizing guideline. A critical concern is the performance of fast protective schemes (instantaneous or differential elements) during severe saturation of low-ratio CTs. Will the instantaneous element operate before the upstream breaker relay trips? Will the differential element misoperate for out-of-zone faults? The use of electromagnetic and analog relay technology does not assure selectivity. Modern microprocessor relays introduce additional uncertainty into the design/verification process with different sampling techniques and proprietary sensing/recognition/trip algorithms. This paper discusses the application of standard CT accuracy classes with modern ANSI/IEEE CT calculation methodology. This paper is the first of a two-part series; Part II provides analytical waveform analysis discussions to illustrate the concepts conveyed in Part I
9
Filtering for protective relays
E.O. Schweitzer, D. Hou · 2002 · 167 citations
Engineering, Electrical Engineering, Critical Infrastructure Protection +15
P.G. McLaren, K.K. Mustaphi, G. Benmouyal et al. · IEEE Transactions on Power Delivery · 2001 · 76 citations
Engineering, Electrical Engineering, Systems Engineering +16