Abstract Heat transfer measurements were made with vertical stainless steel bayonet tubes, 3/8 to 3/4 in. O.D., with lengths from 2.6 to 6.5 in. The heat source was steam. The boiling film Δ T ranged from 154° to 314°F. for three organic liquids and from 547° to 788°F. for nitrogen, all at 1 atm. No forced convection was used. Benzene, carbon tetrachloride, and nitrogen on the longer tubes had h values two or three times greater than predicted by the Bromley equation; however, the Reynolds numbers were found to exceed 2,000. Nitrogen on the 2.6‐in. length obeyed the equation; the Reynolds numbers were less than 2,000, the flow was proved by photography to be turbulent and the h values were much higher than predicted for viscous flow. A correlation is given which fits all the data except for methanol. It shows that a vertical orientation is superior to the horizontal for liquids boiling outside tubes.