Experimental 7.2 kV/sub rms//1 kA/sub rms//3 kA/sub peak/ current limiter system

T. Verhaege, J.P. Tavergnier, C. Agnoux, C. Cottevieille, Y. Laumond, M. Bekhaled, Pierre Bonnet, Manuel Collet, Van-Thanh Pham

IEEE Transactions on Applied Superconductivity · 1993 · 24 citations · 6 references

Concepts

Abstract

A current limiter system based on GEC ALSTHOM's kA-class AC superconducting conductors was realized. Its active components are two parallel noninductive superconducting windings, a shunt resistor, and a detection box which triggers the opening of a fast circuit breaker. The current limiter system has to withstand in the superconducting state current up to 1 kA/sub rms/, and to provide without damage an immediate limitation at 3 kA/sub peak/, in the various fault conditions which could to appear on one of the three phases of a 7.2-kV/sub rms/ network. The conductor definition guarantees complete transitions, and therefore maximal protection, whether in the case of a short circuit or of an accidental quench. Applications to the AC power network are examined for protection against excessive short-circuit currents. The current limiting system reduces considerably the fault current, its destructive effects, and the switching capacity of the required circuit-breaker. The current limiter system has been tested in a 600-MVA power station.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

References

6