Publication | Closed Access
Shutting Down Operating Theater Ventilation When the Theater Is Not in Use: Infection Control and Environmental Aspects
45
Citations
11
References
2003
Year
Shutting down OR ventilation during off-duty periods does not appear to result in an unacceptably high particle count or microbial contamination of the OR air shortly after the system is restarted. Because substantial energy and cost savings are likely, this should be considered in hygienically safe heating, ventilation, and air conditioning systems. However, normal ventilation should be established at least 30 minutes before surgical activity.