Testing the performance of a green wall system on an experimental building in the summer

Cristina Nori, Francesca Olivieri, Roberta Cocci Grifoni, César Bedoya Frutos

UPM Digital Archive (Technical University of Madrid) · 2013 · 14 citations · 0 references

Full text

Open access

Concepts

Abstract

It is known that a green wall brings some advantages to a building. It constitutes a barrier against solar
\nradiation, thus decreasing and delaying the incoming heat flux. The aim of this study is to quantify such advantages
\nthrough analytical comparison between two facades, a vegetal facade and a conventional facade. Both were highly
\ninsulated (U-value = 0.3 W/m2K) and installed facing south on the same building in the central territory of Spain. In
\norder to compare their thermal trend, a series of sensors were used to register superficial and indoor air temperature.
\nThe work was carried out between 17th August 2012 and 1st October 2012, with a temperature range of 12°C-36°C
\nand a maximum horizontal radiation of 1020 W/m2. Results show that the indoor temperature of the green wall
\nmodule was lower than the other. Besides, comparing superficial outdoor and indoor temperatures of the two walls to
\noutdoor air temperatures, it was noticed that, due to the shading plants, the green wall superficial temperature was 5
\n°C lower on the facade, while the bare wall temperature was 15 °C higher. The living wall module temperature was
\n1.6 °C lower than the outdoor, while the values of the conventional one were similar to the outdoor air temperature.