Method for Calculating the Ground Resistance of Grounding Grids Using FEM

Alfredo Güemes, F.E. Hernando

IEEE Transactions on Power Delivery · 2004 · 62 citations · 12 references

Concepts

TL;DR

The paper introduces a finite‑element method for calculating grounding grid resistance, assuming it is independent of earth‑fault current. Ground resistance is computed via three successive FEM tests with a suitable mesh, enabling rapid resolution, and the resulting resistance is used to derive grid potential and touch‑and‑step voltages. The FEM approach yields results comparable to experimental data and other studies, and offers fast, accurate analysis of symmetrical and nonsymmetrical grids in uniform, two‑layer, and multilayer soils, making it a practical industrial tool.

Abstract

Taking as given that ground resistance is independent of earth fault current, this paper presents a new way of calculating ground resistance of grounding grids using the finite-element method (FEM). Ground resistance is calculated by means of three consecutive tests, with an acceptable number of elements, and fast resolution. The results of the proposed method are compared with those measured experimentally or determined by other authors. Once ground resistance and earth fault current are known, grid potential and touch-and-step voltages are calculated. The main advantage of the method proposed here is that it permits us to analyze symmetrical and nonsymmetrical grids of any shape in uniform, two-layer, and multilayer soils. The method developed in this paper constitutes a fast-resolution industrial application, with acceptable results, for calculating the ground resistance of grounding grids of any shape.

References