IEEE Transactions on Power Delivery · 1990 · 17 citations · 3 references
EngineeringMaterials ScienceMechanical EngineeringMechanical Behavior Of MaterialsStructural EngineeringStructural MaterialsComposite MaterialsDynamic Mechanical AnalysisInsulation MaterialsInsulation SystemsMechanics Of Composite MaterialsStructural Response AnalysisComposite Mechanical PropertiesDynamic LoadsDynamic Response Of Composite StructuresFlexion LoadingInsulator Engineering
Four types of composite insulator made with the two most commonly used end fitting designs have been subjected to dynamic mechanical loads. It was found that a combination of dynamic flexion and static tension loads had a more severe effect on the insulators than pulsed tension loads, which in turn were more severe than static tension loads. The design of the end fitting has a significant influence on the response of the insulator to dynamic loads. The results also indicate that it may be more relevant for a user to select composite insulators on the basis of their performance under dynamic loads than under static tension loads.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
3
Nonceramic insulators for transmission lines
H. Schneider, J.F. Hall, G.G. Karady et al. · IEEE Transactions on Power Delivery · 1989 · 112 citations
Engineering, Electrical Engineering, Materials Engineering +16